4. Addressing
Each unit connected to the CUEwire bus must have its unique address. These addresses for
touchpanels and keyboards are set in configuration and are called „panel addresses“. The same type
of address is set for each sensorCUE-W. Its value must be unique for each unit on the CUEwire bus.
The ADDRESS of the sensorCUE-W is binary coded by DIP switch located on the rear panel.
The ADDRESS can be set in the range 1 to 127. Default ADDRESS is 15.
Switch view Switch nr. Function Address bit’s weight
SW1 ADDRESS bit 0 1
SW2 ADDRESS bit 1 2
SW3 ADDRESS bit 2 4
SW4 ADDRESS bit 3 8
SW5 ADDRESS bit 4 16
SW6 ADDRESS bit 5 32
SW7 ADDRESS bit 6 64
SW8 Not used Not used
ADDRESS SW1 SW2 SW3 SW4 SW5 SW6 SW7
1 ON OFF OFF OFF OFF OFF OFF
2 OFF ON OFF OFF OFF OFF OFF
3 ON ON OFF OFF OFF OFF OFF
4 OFF OFF ON OFF OFF OFF OFF
5 ON OFF ON OFF OFF OFF OFF
6 OFF ON ON OFF OFF OFF OFF
7 ON ON ON OFF OFF OFF OFF
8 OFF OFF OFF ON OFF OFF OFF
9 ON OFF OFF ON OFF OFF OFF
… … … … … … …
15 ON ON ON ON OFF OFF OFF
… … … … … … …
126 OFF ON ON ON ON ON ON
127 ON ON ON ON ON ON ON